GV-AS/EV ControllerBefore attempting to connect or operate this product, pleaseread these instructions carefully and save this manual for future use.U
viii Welcome This user manual includes the following types of GV-AS / GV-EV Controllers: GV-AS Controllers Doors Supported One-Way Control Two-Wa
82 4.2.6 Connecting the PC Connecting GV-AS210 / 2110 to a computer allows you to access its Web interface and connect it to GV-ASManager if the co
GV-AS210 / 2110 Controller 8344.2.7 Fitting the Battery (GV-AS2110 Only) GV-AS2110 includes a replaceable cell button battery. When the power in th
84 4.3 Other Settings 4.3.1 Web Setting Switch When the Web Setting switch is set to the ON position, you can modify Advanced Settings and Extende
GV-AS210 / 2110 Controller 8544.3.3 Restoring Factory Defaults To restore GV-AS210 / 2110 to factory default settings, press the Default button for
86 4.4 The Web Interface You can install GV-AS210 / 2110 on a network and configure GV-AS210 / 2110 through its Web interface. Refer to Chapter 8
GV-AS210 / 2110 Controller 8744.5 GV-AS210 / AS2110 Specifications GV-AS210 GV-AS2110 CPU 32-bit ARM7TDMI Number of User Cards 40,000 cards E
5. GV-AS400 Controller
GV-AS400 Controller 8955.1 Introduction 5.1.1 Main Features • 4 doors (one-way and two-way control) • Support 8 Wiegand card readers of 26 to 64
90 5.1.3 GV-AS400 Board Layout 12345678ON EGE12345678ON EGERS-485NONCCOMNONCCOMNONCCOMNONCCOMNONCCOMNONCCOMNONCCOMNONCCOMWiegand A Wiegand BWiegand
GV-AS400 Controller 9155.2 Installation When you wire any devices to GV-AS400 circuit board, please note: • Carefully remove the blue terminal bl
ixImportant Notes for Maintaining Power Supply To make sure GV-AS / EV Controllers can function properly during a power outage, be sure to replace t
92 5.2.1.A Wiegand Readers GV-AS400 provides 8 Wiegand inputs (Wiegand A to Wiegand H) for connection of Wiegand readers ranging from 26 to 64 bits
GV-AS400 Controller 9355.2.1.B RS-485 Readers For long-distance connection and non-Wiegand card readers, you can choose the RS-485 connection. Up t
94 5.2.2 Connecting Input Devices GV-AS400 provides up to 16 inputs. All inputs are dry contact that can be configured as normally open (NO) or nor
GV-AS400 Controller 9555.2.3 Connecting Output Devices GV-AS400 provides up to 16 outputs. They are divided into two groups, outputs 1 ~ 8 and outp
96 To connect an output device: Connect the (+) point on the output device to COM on GV-AS400, connect the two (-) points of the output device and
GV-AS400 Controller 975If your card readers are equipped with LED or beeper that can be controlled externally, connect the control wires to outputs
98 5.2.4 Connecting the Power There are two ways to connect GV-AS400 to power: using GV-AS Power Board or directly. Power should only be applied to
GV-AS400 Controller 995Connect GV-AS400 to Power Directly: To connect GV-AS400 to a power source directly, you must use a 12V DC adaptor. Figure
100 5.2.6 Connecting the External I/O Box To enhance the controller’s I/O capability, up to 4 units of GV-IO Boxes can be optionally connected to G
GV-AS400 Controller 10155.2.7 Fitting the Battery GV-AS400 includes a cell button battery, providing power to GV-AS400 settings and real-time clock
x Note: Make sure the plastic insulation film under the battery is removed when using GV- AS100 / 400 / 2110 / 4110 / 8110 for the first time. The
102 5.3 Other Settings 5.3.1 Web Setting Switch When the Web Setting switch is set to the ON position, you can modify Advanced Settings and Extend
GV-AS400 Controller 10355.3.3 Restoring Factory Defaults You can choose to restore only Basic Settings or All Settings to factory default values. F
104 5.4 The Web Interface You can install GV-AS400 on a network and configure GV-AS400 through its Web interface. Refer to Chapter 8 Installing o
GV-AS400 Controller 10555.5 Optional GV-ASKeypad GV-ASKeypad is an optional device for an administrator to control and manage GV-AS400. An administ
106 5.5.2 Operation GV-ASKeypad allows you to configure basic settings and view system information. Press the following codes on the keypad to star
GV-AS400 Controller 1075AS400 Function Sets the function for each door. For types of functions, see 8.2 Advanced Settings. Press the Right and Left
108 5.6 GV-AS Power Board GV-AS Power Board is designed for GV-AS400 to provide additional power supply for output devices, such as locking devices
GV-AS400 Controller 10955.6.2 Connecting Output Devices GV-AS Power Board provides two types of power outputs: 24V AC/DC, 10V to 13V DC. The figure
110 To connect an output device: Connect the (+) point on the output device to COM on GV-AS400, connect the two (-) points of the output device and
GV-AS400 Controller 11155.6.4 Connecting Backup Battery GV-AS Power Board supports any battery of 12V 12Ah to provide battery backup when the mains
xiElevator Control GV-AS / GV-EV Controllers provide two types of elevator control. For GV-AS100 / 1010 / 110 / 1110 / 120 / 210 / 2110 / 400 / 41
112 5.7 GV-AS400 Specifications CPU 32-bit ARM7TDMI & 8-bit RISC microprocessor Number of User Cards 40,000 cards Event Buffer 65,536 even
6. GV-AS410 / 4110 / 810 / 8110 Controller
114 6.1 Introduction 6.1.1 Main Features • One-way control: GV-AS410 / 4110: 4 doors GV-AS810 / 8110: 8 doors • Two-way control: GV-AS410 / 41
GV-AS410 / 4110 / 810 / 8110 Controller 11566.1.3 GV-AS410 / 4110/ 810 / 8110 Board Layout Figure 6-1
116 6.2 Installation 6.2.1 Connecting Card Readers GV-AS410 / 4110 / 810 / 8110 supports two types of card reader interfaces: • Wiegand: Compat
GV-AS410 / 4110 / 810 / 8110 Controller 11766.2.1.B RS-485 Readers For long-distance connection and non-Wiegand card readers, you can connect RS-48
118 Note: 1. Each set of 12V power output and GND can provide power for up to 2 readers. The 3 sets on the power terminal can support up to 6 rea
GV-AS410 / 4110 / 810 / 8110 Controller 11966.2.2 Connecting Input Devices Up to 16 input devices can be connected to GV-AS410 / 4110 / 810 / 8110.
120 6.2.3 Connecting Output Devices Up to 24 output devices can be connected to GV-AS410 / 4110 / 810 / 8110. Check if your output device meets the
GV-AS410 / 4110 / 810 / 8110 Controller 12166.2.4 Connecting Backup Battery You can connect any battery of 12V 12Ah to GV-AS410 / 4110 / 810 / 8110
xii Optional Devices Optional devices can expand the capabilities and versatilities of your GV-AS / GV-EV Controllers. Consult your sales representa
122 6.2.6 Connecting the PC Connecting GV-AS410 / 4110 / 810 / 8110 to a computer allows you to access its Web interface and connect it to GV-ASMan
GV-AS410 / 4110 / 810 / 8110 Controller 12366.3 Other Settings 6.3.1 Web Setting Switch When the Web Setting switch is set to the ON position, you
124 6.3.3 Restoring Factory Defaults To restore GV-AS410 / 4110 / 810 / 8110 to factory default settings, press the Default button for 10 seconds.
GV-AS410 / 4110 / 810 / 8110 Controller 12566.4 GV-AS410 / 4110 / 810 / 8110 Kit (Optional) GV-AS410 / 4110 / 810 / 8110 Kit is a cabinet containi
126 6.4.3 Connecting the GV-AS410 / 4110 / 810 / 8110 Kit Up to 8 output devices can be powered by the power adapter board. Connect each output dev
GV-AS410 / 4110 / 810 / 8110 Controller 12762. Connect the ED + / - pins to the (+) and (-) points on the output device (ex: electric lock). ++--ED
128 6.4.4 GV-AS410 / 4110 / 810 / 8110 Kit Specifications Power Adapter Board DC Voltage Range 12V Rated Current 0.9A Output Rated Power 10.8 W In
GV-AS410 / 4110 / 810 / 8110 Controller 12966.5 The Web Interface You can install GV-AS410 / 4110 / 810 / 8110 on a network and configure GV-AS410
130 6.6 GV-AS410 / 4110 / 810 / 8110 Specifications Software Control Mode GV-AS410 / 4110 GV-AS810 / 8110 One-Way Control 4 doors 8 doors Two-W
7. GV-EV48 Controller
xiiiGV-Hub Only works with GV-AS100 / 110 / 120. GV-Hub can convert the standard RS-232 signal of up to 4 controllers to RS-485, allowing the contro
132 7.1 Introduction GV-EV48 is an elevator controller designed to control access of 1 elevator with a maximum of 48 floors. Up to 2 GV-Readers / G
GV-EV48 Controller 13377.1.3 GV-EV48 Board Layout Figure 7-1
134 7.2 Installation 7.2.1 Connecting RS-485 Card Readers With a single RS-485 cable, you can connect up to 2 GV-Readers and / or GV-GF Fingerpri
GV-EV48 Controller 13577.2.2 Connecting Output Relay Up to 24 output relays can be connected to the GV-EV48-24 Floors to control up to 24 elevator
136 7.2.3 Connecting Backup Battery Using the supplied battery cable, you can connect any battery of 12V 12Ah to GV-EV48 to provide backup power wh
GV-EV48 Controller 13777.2.5 Connecting the PC Connecting GV-EV48 to a computer allows you to access its Web interface and connects it to GV-ASMana
138 7.3 Other Settings 7.3.1 Web Setting Switch When the Web Setting switch is set to the ON position, you can modify Advanced Settings and Extend
GV-EV48 Controller 13977.3.3 Restoring Factory Defaults To restore GV-EV48 to factory default settings, press the Default button for 10 seconds.
140 7.4 The Web Interface You can install GV-EV48 on a network and configure GV-EV48 through its Web interface. Refer to Chapter 8 Installing on
GV-EV48 Controller 14177.5 GV-EV48 Specifications CPU 32-bit ARM7TDMI Number of User Cards 40,000 cards Event Buffer 1,000,000 events and log
xiv Installation Considerations 1. There are distance limitations for Wiegand and RS-485 communications. Please note: • Wiegand interface: Recomme
8. Installing on a Network
Installing on a Network 1438You can install GV-AS1010 / 1110 / 210 / 2110 / 400 / 410 / 4110 / 810 / 8110 and GV-EV48 on a network and set up genera
144 8.1 Fixed IP Connection If your network environment supports a static IP address, the wiring is illustrated as below: Figure 8-1 To assign th
Installing on a Network 14582. Click default value admin for both User name and Password, and click OK. This page appears.
146 8.2 DHCP Connection If your network environment is using the dynamic IP address from a DHCP server, use one of the following DDNS servers to ma
Installing on a Network 1478Installing LocalDDNS Server To install the LocalDDNS Server in a computer, download GV-Local DDNS Service from http://ww
148 6. Click Submit to send the information to the LocalDDNS Server. When the setting is complete, the Status field will indicate: Register Success.
Installing on a Network 14988.2.2 Connection over Internet DDNS (Dynamic Domain Name System) provides another way of accessing GV-AS / GV-EV Contr
150 2. In the Username field, type a name. Username can be up to 16 characters with the choices of “a ~ z”, “0 ~9”, and “-”. Note that space or “-”
Installing on a Network 1518Configuring the GV-AS / GV-EV Controller on Internet After acquiring a domain name from the DDNS Server, you need to con
xvFirmware and Software Compatibility The GV-AS / GV-EV Controllers firmware versions compatible with GV-ASManager V4.0 - V4.2.3 are listed below.
9. The Web Interface
The Web Interface 1539After installing the GV-AS / GV-EV Controller on the network, you can configure the controller settings on the Web interface.
154 9.1 Basic Settings The Basic Settings section covers general system settings, firmware update and user account settings. For details on Network
The Web Interface 1559 3DES Code 1-3: Stands for Triple DES (Data Encryption Standard). Type up to three different keys for data encryption. The d
156 9.1.2 Upgrading Firmware Follow the steps below to update the firmware of the controller. To upgrade the firmware of GV-AS400, an extra step i
The Web Interface 15794. When the Update is complete, a dialog box appears and asks you to reboot the system. Figure 9-5 5. Click OK. The controll
158 9.1.3 Changing Login ID and Password To change the login ID and password: 1. In the left menu, click Account Setting. 2. On the Security Co
The Web Interface 15999.2 Advanced Settings To configure the Advanced Setting on the Web interface, set the Web Setting switch on the GV-AS / GV-EV
160 For GV-EV48, the options available in Advanced Settings page are fixed. Only the following setting pages are available: Figure 9-8
The Web Interface 16199.2.1 Function Setting In the left menu, click Function Setting. The Function Configuration page appears. The number of door
xvi Definition Tampering Alarm GV-AS100 / 1010 / 110 / 1110 / 120 have built-in sensors to detect whether the controller is being physically tamper
162 [ID] Enter the ID number for the controller. This ID is used by GV-ASManager to differentiate among multiple units of controller. ID number ca
The Web Interface 1639[Series Function (APB & Fire)] This option lets you set the Anti-Passback function and fire sensor function across multipl
164 9.2.2 Parameter Setting In the left menu, click Parameter Setting for GV-AS Controllers or click Elevator Parameter for GV-EV48. The Parameter
The Web Interface 1659[Interlock] When the option is enabled, the two mentioned doors will be interlocked, allowing only one door to be opened at a
166 • When Elevator Control is selected in the Function Setting page (Figure 9-9), these options become available: Option Description Relay on Tim
The Web Interface 1679• When Parking Control is selected in the Function Setting page (Figure 9-9), these options become available: Option Descri
168 9.2.2.B GV-EV48 The Parameter Setting page allows you to specify which elevator floors are restricted. Figure 9-12 [Events] • Relay On Tim
The Web Interface 1699[Common Password] When Fixed Card/Common Mode is selected as Authentication Mode in the Function Setting page (Figure 9-9), yo
170 9.2.3 Card Setting In the left menu, click Card Setting to set the built-in card reader of GV-AS1010 and GV-AS1110 to read UID (unique identifi
The Web Interface 17199.2.4 Card Information In the left menu, click Card Information to see the cards added by GV-AS1010 and GV-AS1110. Figure
1. GV-AS100 / 1010 Controller
172 9.2.5 Time Setting In the left menu, click Time Setting to set up system time, local time and daylight saving time period. Figure 9-16 [Syste
The Web Interface 1739[Local Time] Disable: Disable the manual configuration of time and date. Setup: Enable the manual configuration of Time
174 9.2.6 Input Setting In the left menu, click Input Setting to define the input devices connected to the GV-AS Controller. The number of input de
The Web Interface 1759 1. Input Type 2. Input Function Figure 9-19 1. Input Type: Configure the input type. Input Type defines the type of sensor t
176 Gate # Fire Sensor Tamper Zone Exit Button Car Detection See the “Door #” Input Type above. For example, when the Car Detection sensor detects
The Web Interface 17799.2.7 Output Setting In the left menu, click Output Setting. The Output Configuration page appears. The number of output devi
178 Here you can name and define each output device connected to the GV-AS Controller, such as locking devices and Exit Button. Select from the drop
The Web Interface 17999.2.7.A Output Function Settings This section explains the output functions available when Output Type is set to Door #, Gate
180 • When Gate # is selected as Output Type, these Output Functions become available: Output # Output Type Output Function Description Electric L
The Web Interface 18199.2.7.B Output Condition Settings This section explains the output functions available when Output Type is set to Normal, Tog
© 2014 GeoVision, Inc. All rights reserved. Under the copyright laws, this manual may not be copied, in whole or in part, without the w
2 1.1 Introduction Working as a standalone solution, GV-AS100 / 1010 is a card reader with a LCD display and also a single door controller. It is
182 Click Reset button to return the Normal, Toggle or Pulse triggered state to be normal. Click Submit button to save the changes, or click Canc
The Web Interface 18399.2.8 Wiegand Function In the left menu, click Wiegand Setting to define the connected Wiegand readers. The number of Wiegan
184 9.2.9 Function Key In the left menu, click Function Key to define the function keys on GV-AS1010. Figure 9-25 Set the function keys to be
The Web Interface 18599.2.10 Urgent Card In the left menu, click Urgent Card. When the battery on GV-AS400 runs out of power for more than 10 hours
186 9.3 Extended Device You can define the GV-Readers and GV-GF Fingerprint Readers connected to GV-AS / GV-EV Controller through RS-485 or network
The Web Interface 1879[GV-Reader / CR420 / GF1921 / 1922 Function] Define the readers connected to the controller, and then use the Function drop-do
188 Figure 9-29 Note: 1. To allow network connection, you must also enable network connection to the controller on the Web interface of the GV-
The Web Interface 18999.3.2 Extended I/O In the left menu, click Extended I/O. The Extended I/O Configuration page appears. The page defines the in
10. Optional Devices
Optional Devices 1911010.1 Optional GV-ASBox The optional GV-ASBox is the I/O and network expansion module for GV-AS100, GV-AS110 and GV-AS120. Wit
GV-AS100 / 1010 Controller 31GV-AS100 can make network connection to GV-ASManager using the optional GV-ASBox or GV-ASNet. With GV-ASBox, two-door c
192 10.1.3 GV-ASBox Board Layout 12ONNO5COM5NC5NO6COM6NC6NO7COM7NC7NO8COM8NC812V12VGNDGNDNC4COM4NO4NC3COM3NO3NC2COM2NO2NC1COM1NO1Com.ACom.ADI4DI3DI
Optional Devices 1931010.1.4 Installation This section describes how to connect other devices to GV-ASBox. 10.1.4.A Connecting GV-AS100 / 110 /
194 10.1.4.B Connecting a Wiegand Reader GV-ASBox provides one Wiegand input for connection of the Wiegand-compatible reader ranging from 26 to 64
Optional Devices 1951010.1.4.C Connecting GV-Readers and GV-GF Fingerprint Readers You can connect up to 4 units of GV-Readers and GV-GF Fingerpri
196 10.1.4.D Connecting Input Devices GV-ASBox provides 8 inputs (DI1 to DI8). All inputs are dry contact and can be configured as normally open (N
Optional Devices 1971010.1.4.E Connecting Output Devices GV-ASBox provides 8 outputs and 2 auxiliary power outputs of 12V DC. The outputs are divid
198 To connect an output device: GV-ASBox provides two auxiliary power outputs of 12V DC at a maximum current of 1A. If your output device requires
Optional Devices 1991010.1.4.F Connecting Backup Battery You can connect any battery of 12V 12Ah to GV-ASBox to provide backup power when the main
200 10.1.4.G Other Settings The figure below shows the location of the Web Setting Switch, Reset Button and Default Button. DefaultReset EN Figure
Optional Devices 2011010.1.5 GV-ASBox Specifications CPU 32-bit ARM7TDMI Microprocessor Power 100 ~ 240V AC, 50 ~ 60 Hz Battery 12V, 5Ah RS-485 I
4 1.1.1 Main Features GV-AS100 • 1 door (one-way and two-way control), expandable to 2 doors with optional GV-ASBox • 1,000 / 40,000 cards (stand
202 10.2 Optional GV-ASNet The optional GV-ASNet is the network expansion module for GV-AS100, GV-AS110 and GV-AS120. With the GV-ASNet, GV-AS100 /
Optional Devices 2031010.2.3 GV-ASNet Overview Front View Rear View Figure 10-9 No. Name Function 1 DC Power Input (12V) Conne
204 10.2.4 Installation This section describes how to connect other devices to GV-ASNet. 10.2.4.A Connecting GV-AS100 / 110 / 120 The table and
Optional Devices 2051010.2.4.B Connecting GV-Readers and GV-GF Fingerprint Readers You can connect up to 2 units of GV-Readers and GV-GF Fingerpri
206 10.2.4.C Connecting Backup Battery You can connect any battery of 12V 12Ah to GV-ASNet to provide backup power when the main power supply fails
Optional Devices 2071010.2.4.D Other Settings The figure below shows the location of the Web Setting Switch, Default Button and Power Status LED.
208 10.2.5 GV-ASNet Specifications CPU 32-bit ARM7TDMI Microprocessor Power 100 ~ 240V AC, 50 ~ 60 Hz Battery 12V, 5Ah and 12V, 12Ah RS-485 Inte
Optional Devices 2091010.3 Web Interface through Optional Devices Through GV-ASBox or GV-ASNet, you can access the GV-AS100 / GV-AS110 / GV-AS120’s
210 10.3.2 Advanced Settings You can execute and edit door/Wiegand operations and settings, turn on Alarms, view status, display card information s
Optional Devices 2111010.3.2.A Function Setting In the left menu, click Function Setting. This AS100/AS110/AS120 Function Configuration page appea
GV-AS100 / 1010 Controller 511.1.2 Packing List GV-AS100 • GV-AS100 • Power Adaptor 12V DC / 1A • Power Cord • Screw x 3 • Screw Anchor x 2 • Ma
212 [ASBox Wiegand] This option is only available for GV-ASBox. Select the function for Wiegand Input on GV-ASBox from the drop-down list. No Fun
Optional Devices 21310 Fixed Card + PIN Mode: Grants access after the user presents the card and then enters the card’s PIN code, and ignores the
214 10.3.2.B Parameter Setting In the left menu, click Parameter Setting. This AS100/AS110/AS120 Configuration page appears. The contents of Param
Optional Devices 21510[Events] Set the parameters for the events. Figure 10-17 • When Door Entry/Exit Control or Parking Entry/Exit Control is se
216 [Alarm] Select Yes or No to enable or disable the alarm function. If you have defined the alarm conditions in [Output Function] of the In/Out Fu
Optional Devices 21710[Common Password] When Fixed Card/Common Mode is selected as Authentication Mode in the Function Setting page (Figure 10-15),
218 10.3.2.C Status Monitor In the left menu, click Status Monitor to see the status of each input, output and alarm Figure 10-20 Control Mode
Optional Devices 2191010.3.2.D Card Information In the left menu, click Card Information. This Card Configuration page appears. Figure 10-21 [Car
220 10.3.2.E Time Setting In the left menu, click Time Setting. This Time Configuration page appears. Figure 10-22 [System Local Time] Local T
Optional Devices 2211010.3.2.F In/Out Function In the left menu, click In/Out Function to define the input and output sensors. Figure 10-23 [In
6 1.1.3 GV-AS100 / 1010 Board Layout GV-AS100 GV-AS1010 Figure 1-4
222 Below is the explanation based on the numbers marked on the above figure. 1. ASBOX Input #: Edit the name of the Input. 2. NO/NC: Configure the
Optional Devices 22310• When Elevator Control is selected in the Function Setting page (Figure 10-15), these Input Type and Input Function become a
224 Output Function Settings: When Output Type (No. 1, Figure 10-25) is set to be Door #, Gate # or Relay #, the options similar to the figure below
Optional Devices 22510• When Parking Entry/Exit Control is selected in the Function Setting page (Figure 10-15), these Output Type and Output Funct
226 Output Condition Settings: When Output Type (No. 1, Figure 10-25) is set to be Normal, Toggle, Pulse, Normal Lighting, Toggle Lighting or Pulse
Optional Devices 22710In the Output Condition Settings, these Output Type and Output Condition options become available: Output Condition Output Ty
228 10.3.2.G Extended Reader In the left menu, click Extend Reader. This Extend Reader Configuration page appears. Figure 10-28 Define the reader
Optional Devices 22910[GeoFinger Function] For GV-GF1901 / GF1902 / GF1911 / GF1912, select the checkbox and type the XID Number located on the back
11. Troubleshooting
Troubleshooting 23111 Q1: GV-ASManager cannot connect to GV-AS/ GV-EV Controller over the Internet. There are several causes for this problem such
GV-AS100 / 1010 Controller 711.2 Installation Open the GV-AS100 / 1010 to access the terminal block. GV-AS100 Pin Function Pin Function 1 12V Po
232 4. Open the browser and enter the controller default address: http://192.168.0.100 Figure 11-2 5. In the IP address field, give the controlle
Troubleshooting 23311 7. The connection between the GV-ASManager and controller should be established, and the connection icon should appear. If
234 User: admin Password: admin Crypto key: 12345678 8. The connection between the GV-ASManager and GV-AS Controller should be established, and the
Troubleshooting 23511 Q6: The GV-ASManager cannot receive card messages from the GV-Reader connected to the GV-AS / GV-EV Controller through RS-485
Appendix
Appendix 237A. GV-MountA900 for GV-AS110 / 1110 (Optional) GV-MountA900 is an optional mounting plate that allows you to attach GV-AS110 / 1110 to
8 1.2.1 Connecting Card Readers 1.2.1.A Wiegand Readers (GV-AS100 Only) GV-AS100 provides one Wiegand input for connection of the Wiegand reader
GV-AS100 / 1010 Controller 911.2.1.B RS485 Readers For long-distance connection and non-Wiegand card readers, you can establish RS-485 connection
10 1.2.1.C Network Readers (GV-AS1010 Only) GV-AS1010 supports network connection with GV-CR420 and GV-GF1921 / 1922. Through the GV-AS1010 keypad,
GV-AS100 / 1010 Controller 1111.2.2 Connecting Input Devices GV-AS100 / 1010 supports 3 types of inputs: 1. Sensor inputs, e.g. door status sensor
iContents Welcome... viii Important No
12 1.2.3 Connecting Output Devices GV-AS100 supports 2 types of outputs: 1. Alarm outputs, e.g. siren or bell 2. Door outputs, e.g. electronic lo
GV-AS100 / 1010 Controller 131To connect an output device: The example below illustrates the connection of a locking device to GV-AS100 / 1010. Con
14 1.2.4 Connecting the PC Connecting GV-AS110 / 1110 to a computer allows you to access its Web interface and connect it to GV-ASManager if the co
GV-AS100 / 1010 Controller 1511.2.4.A Connecting GV-AS100 to PC RS-485 Connection between GV-AS100 and PC The figure below illustrates the RS-485 c
16 Network Connection between GV-AS100 and PC The figure below illustrates the network connection to the computer. For this connection, the optional
GV-AS100 / 1010 Controller 1711.2.4.C Switches (GV-AS100 Only) Switch 1: When Switch 1 is ON, GV-AS100 can connect to GV-ASManager, GV-ASBox or GV-
18 1.2.6 Fitting the Battery GV-AS100 / 1010 includes a battery, providing power to GV-AS100 / 1010 settings and real-time clock circuitry. When th
GV-AS100 / 1010 Controller 1911.2.7 Using the Function Keys (GV-AS1010 Only) GV-AS1010 comes with four function keys. On the Web interface of GV-AS
20 1.3 Programming Mode After powering on GV-AS100, you must create a Master Card first. It is required to present the Master Card and enter its PI
GV-AS100 / 1010 Controller 211The table below shows the codes to start various programming and display system information. Code Function *227 (*C
ii 1.3.6 Displaying System Information...29 1.3.7 Restoring Factory Defaults...
22 1.3.1 Quick Reference of Programming Table GV-AS100 Card Manger Add New Card 1) N, 2) A, 3) B, 4) S Del Card Data Reset Card’s
GV-AS100 / 1010 Controller 231GV-AS1010 Card Manger Reset Card’s APB Display System Door’s Auth Mode Door’s Event Memory’s State
24 1.3.2 Adding and Deleting a Card Note: 1. GV-ASManager cannot manage the cards enrolled on GV-AS100 / 1010, since the card data will not be t
GV-AS100 / 1010 Controller 2511.3.2.B Deleting a Card GV-AS100 1. Press the code *227 (*CAR). 2. Present the Master Card and enter its PIN code.
26 1.3.4 Accessing the Security Mode The security mode is used to arm GV-AS100 / 1010. In the arm mode, no cards can be granted access and no one c
GV-AS100 / 1010 Controller 2711.3.5 Setting Parameters You can define the parameters of some features on GV-AS100 / 1010. IMPORTANT: Once connecti
28 AS100 / 1010 Function GV-ASBox: Enables or disables the connection to GV-ASBox / GV-ASNet. (GV-AS100 only) Control Type: Door Entry Ty
GV-AS100 / 1010 Controller 2911.3.6 Displaying System Information To display system information, press the code *347 (*DIS). Option Function Doo
30 1.3.7 Restoring Factory Defaults The restore function is used to clear all configured options and cards from GV-AS100 / 1010 memory and bring ba
GV-AS100 / 1010 Controller 3111.4 Web-Based Configurations GV-AS100 Through GV-ASBox or GV-ASNet, GV-AS100 can communicate with GV-ASManager over t
iii3.3 Programming Mode...69 3.3.1 Adding and Deleti
32 1.5 GV-AS100 / 1010 Specifications GV-AS100 CPU 8-bit RISC microprocessor Number of User Cards 1,000 / 40,000 cards (standalone / networked o
GV-AS100 / 1010 Controller 331GV-AS1010 CPU 32-bit ARM7TDMI Number of User Cards 1,000 / 40,000 cards (standalone / networked mode) Frequency 13.5
2. GV-AS110 / 1110 Controller
GV-AS110 / 1110 Controller 3522.1 Introduction Working as a standalone solution, GV-AS110 / 1110 is a card reader and also a single door controller
36 GV-AS110 can make network connection to GV-ASManager using the optional GV-ASBox or GV-ASNet. With GV-ASBox, two-door control is also possible as
GV-AS110 / 1110 Controller 3722.1.1 Main Features GV-AS110 • 1 door (one-way and two-way control), expandable to 2 doors with optional GV-ASBox •
38 2.1.2 Packing List • GV-AS110 / GV-AS1110 • Power Adaptor 12V DC / 1.25A • Power Cord • Screw x 2 • Screw Anchor x 2 • Front Cover Plate x
GV-AS110 / 1110 Controller 3922.2 Installation The wire assignment of the GV-AS110 cable data are illustrated below. Front View Figure 2-4 Rear
40 Wire color Definition Red 7.5V~12V DC Black GND Green IN COM Blue IN1 (Sensor) Purple IN2 (Button) Brown Door Com Yellow Door NC Orange Door
GV-AS110 / 1110 Controller 4122.2.1 Connecting Card Readers 2.2.1.A Wiegand Readers (GV-AS110 Only) GV-AS110 provides one Wiegand input for connec
iv 5.2.3.B Outputs 9 ~ 16...96 5.2.4 Connecting the Power...
42 2.2.2 Connecting Input Devices GV-AS110 supports 3 types of inputs, while GV-AS1110 supports 2 types of inputs. 1. GV-AS110 / 1110: Sensor inpu
GV-AS110 / 1110 Controller 4322.2.3 Connecting Output Devices GV-AS110 supports 2 types of outputs, while GV-AS1110 supports 1 type of output: 1.
44 To connect an output device: The example below illustrates the connection of a locking device to GV-AS110 / 1110. Connect the (+) point on the l
GV-AS110 / 1110 Controller 4522.2.4 Connecting to the PC Connecting GV-AS110 / 1110 to a computer allows you to access its Web interface and connec
46 Network Connection between GV-AS110 and PC The figure below illustrates the network connection between GV-AS110 and the computer. For this connec
GV-AS110 / 1110 Controller 4722.2.5 Connecting the Power The supplied AC adaptor can be connected to any power source supplying from 100 to 240V. C
48 2.3 Programming Mode After powering on GV-AS110 / 1110, you must create two cards first, an Enroll Card and a Delete Card. The Enroll Card is us
GV-AS110 / 1110 Controller 4922.3.1.A Adding a Card Up to 1,000 cards can be enrolled on GV-AS110 / 1110 directly without needing additional softwa
50 2.3.1.B Deleting a Card 1. Present the Delete Card. 2. Present the card you want to delete. 3. The GV-AS110 / 1110 will produce a long beep i
GV-AS110 / 1110 Controller 5122.3.2 Programming the GV-AS110 / 1110 The command codes used to program various functions on GV-AS110 / 1110 are list
v6.4.1 Packing List...125 6.4.2 Overview...
52 Set Alarm Event *723_ _ _ _# Held Open Î 0 Forced Open Î 1 Tamper Î 2 Fire Alarm Î 3 Access Denied Î 4 Alarm Time Î 1-10 sec For the first blan
GV-AS110 / 1110 Controller 532For example, to enable the Fixed Card + PIN mode, press *5264#. Open door with card number and PIN code *_ _ _ _ _ _
54 2.4 LED Status and Beeper Normally, the LED on GV-AS110 / 1110 is blue during standby mode. The LED status and beeper under different conditions
GV-AS110 / 1110 Controller 552Factory default Flashes blue Silent GV-AS1110 Condition LED Beeper Access Granted Flashes green momentarily On
56 2.5 Web-Based Configurations GV-AS110 Through GV-ASBox or GV-ASNet, GV-AS110 can communicate with GV-ASManager over the network. Using GV-ASBox
GV-AS110 / 1110 Controller 5722.6 GV-AS110 / 1110 Specifications GV-AS110 CPU 32-bit RISC microprocessor Number of User Cards 1,000 / 40,000 ca
58 GV-AS1110 CPU 32-bit ARM7TDMI Number of User Cards 1,000 / 40,000 cards (standalone / networked mode) Frequency 13.56 MHz for ISO14443A (Mifare
3. GV-AS120 Controller
60 3.1 Introduction Working as a standalone solution, GV-AS120 is a card reader and also a single door controller. It is possible to add one more c
GV-AS120 Controller 613GV-AS120 can make network connection to GV-ASManager using the optional GV-ASBox or GV-ASNet. With GV-ASBox, two-door control
vi 9.2.5 Time Setting...172 9.2.6 Input Setting...
62 3.1.1 Main Features • 1 door (one-way and two-way control), expandable to 2 doors with optional GV-ASBox • 1,000 / 40,000 cards (standalone /
GV-AS120 Controller 6333.2 Installation The wire assignment of the GV-AS120 cable data are illustrated below. Front View Rear View Figure
64 3.2.1 Connecting a Wiegand Reader GV-AS120 provides one Wiegand input for connection to the Wiegand reader ranging from 26 to 64 bits. Through t
GV-AS120 Controller 6533.2.3 Connecting Output Devices GV-AS120 supports 1 type of output: Door outputs, e.g. electronic lock The table below show
66 3.2.4 Connecting to the PC The computer running GV-ASManager software can be used to monitor the access information and alarm messages from GV-A
GV-AS120 Controller 673To define ID number, control type and authentication mode Using the GV-AS120 Setting AP in the GV-ASManager folder, you can
68 3.2.4.B Network Connection The figure below illustrates the network connection to the computer. For this connection, a GV-ASBox or GV-ASNet is r
GV-AS120 Controller 6933.3 Programming Mode After powering on GV-AS120, you must create two cards first, an Enroll Card and a Delete Card. The Enro
70 3.3.1.A Adding a Card Up to 1,000 cards can be enrolled on GV-AS120 directly without needing additional software. When working with GV-ASManager
GV-AS120 Controller 7133.4 LED Status and Beeper Normally, the LED on GV-AS120 is blue during standby mode and the LED flashes green when a card is
vii10.2.4.D.c Power Status LED...207 10.2.5 GV-ASNet Specifications ...
72 3.5 Web-Based Configurations Through GV-ASBox or GV-ASNet, GV-AS120 can communicate with GV-ASManager over the network. Using GV-ASBox or GV-ASN
GV-AS120 Controller 7333.6 GV-AS120 Specifications CPU 32-bit RISC microprocessor Number of User Cards 1,000 / 40,000 cards (standalone / networ
4. GV-AS210 / 2110 Controller
GV-AS210 / 2110 Controller 7544.1 Introduction 4.1.1 Main Features • One-way control: 4 doors • Two-way control: 2 doors by Wiegand only, 4 door
76 4.1.3 GV-AS210 / 2110 Board Layout NC8COM8NO8NC7COM7NO7NC6COM6NO6NC5COM5NO5NC4COM4NO4NC3COM3NO3NC2COM2NO2NC1COM1NO1ONOFFWeb Setting12VD0D1GND12
GV-AS210 / 2110 Controller 7744.2 Installation 4.2.1 Connecting Card Readers GV-AS210 / 2110 supports two types of card reader interfaces: • Wi
78 4.2.1.B RS-485 Readers For long-distance connection and non-Wiegand card readers, you can establish RS-485 connection with any GV-Readers and GV
GV-AS210 / 2110 Controller 7944.2.2 Connecting Input Devices Up to 8 input devices can be connected to GV-AS210 / 2110. Connect the input wires to
80 4.2.3 Connecting Output Devices Up to 8 output devices can be connected to GV-AS210 / 2110. Check if your output device meets the following abso
GV-AS210 / 2110 Controller 8144.2.4 Connecting Backup Battery You can connect any battery of 12V 12Ah to GV-AS210 / 2110 to provide backup power wh
Komentarze do niniejszej Instrukcji